HV.TR
|
High Voltage Power
Transformer
|
HV.TR.VI
|
Visual Inspection
|
HV.TR.IR
|
Measurement Of D.C Insulation
Resistance And Check Of Core Insulation
|
||
HV.TR.WR.TTR
|
Measurement Of Winding Resistance & Measurement Of
Transformer Turns Ratio
|
||
HV.TR.AC
|
Short Circuit (%Z), Zero Sequence
Impedance (Z0), No Load, Vector Group & Magnetic Balance Test
|
||
HV.TR.DF
|
Measurement Of Dissipation Factor
(Tan ∂)
|
||
HV.TR.MD
|
Mechanical Protection Devices Test And MK Function Check
|
||
HV.TR.WT-OT
|
Calibration Of Winding And Oil
Temperature Gauges
|
||
HV.TR.ODBT
|
Oil Dielectric Breakdown Test
|
||
HV.TR.GADT
|
On Line Gas Analyzer Devices Test
(If Any)
|
||
HV.TR.MMAM
|
Fans Motors, Oil Pumps, MCB's, Aux
Relays And Meters Test
|
||
HV.TR.BCT
|
BCT Test
|
||
HV.TR.BCT-SEC
|
BCT Secondary Circuits, Loop
Resistance And Burden Test
|
||
HV.TR.NER
|
Neutral Earthing Resistance Test
|
||
HV.TR.PT
|
Oil Leak Test With Pressure
|
||
HV.TR.FRA
|
Measurement Of Frequency Response
Test (Frequency Response Analysis FRA)
|
||
HV.TR.OLTC
|
On-Load Tap-Changers (OLTC)
Test
|
||
EHV.SR
|
EHV Shunt Reactor
|
EHV.SR.VI
|
Visual Inspection
|
EHV.SR.IR
|
Measurement Of D.C Insulation
Resistance And Check Of Core Insulation
|
||
EHV.SR.RL
|
Measuring Of Winding Resistance
And Reactance
|
||
EHV.SR.DF
|
Measurement Of Dissipation Factor
(Tan ∂)
|
||
EHV.SR.MD
|
Mechanical Protection Devices Test
And MK Function Check
|
||
EHV.SR.WT-OT
|
Calibration Of Winding And Oil
Temperature Gauges
|
||
EHV.SR.ODBT
|
Oil Dielectric Breakdown Test
|
||
EHV.SR.MMAM
|
Fans Motors, Oil Pumps, MCB's, Aux
Relays And Meters Test
|
||
EHV.SR.BCT
|
BCT Test
|
||
EHV.SR.BCT-SEC
|
BCT Secondary Circuits, Loop
Resistance And Burden Test
|
||
EHV.SR.PT
|
Oil Leak Test With Pressure
|
||
EHV.SR.FRA
|
Measurement Of Frequency Response
Test (Frequency Response Analysis FRA)
|
||
EHV.SR.GADT
|
On Line Gas Analyzer Devices Test
(If Any)
|
||
HV.SR
|
HV Shunt Reactor
|
HV.SR.VI
|
Visual Inspection
|
HV.SR.IR
|
Measurement Of D.C Insulation
Resistance And Check Of Core Insulation
|
||
HV.SR.RL
|
Measuring Of Winding Resistance And
Reactance
|
||
HV.SR.DF
|
Measurement Of Dissipation Factor
(Tan ∂)
|
||
HV.SR.MD
|
Mechanical Protection Devices Test
And MK Function Check
|
||
HV.SR.WT-OT
|
Calibration Of Winding And Oil
Temperature Gauges
|
||
HV.SR.ODBT
|
Oil Dielectric Breakdown Test
|
||
HV.SR.MMAM
|
Fans Motors, Oil Pumps, MCB's, Aux
Relays And Meters Test
|
||
HV.SR.BCT
|
BCT Test
|
||
HV.SR.BCT-SEC
|
BCT Secondary Circuits, Loop
Resistance And Burden Test
|
||
HV.SR.PT
|
Oil Leak Test With Pressure
|
||
HV.SR.FRA
|
Measurement Of Frequency Response
(Frequency Response Analysis FRA)
|
||
HV.SR.GADT
|
On Line Gas Analyzer Devices Test
(If Any)
|
||
EHV.GIS
|
Extra High Voltage GIS
|
EHV.GIS.SF6.TEST
|
SF6 Gas Purity And Dew Point Test
|
EHV.GIS.SF6.LEK
|
SF6 Gas Leakage Test
|
||
EHV.GIS.SF6.DG
|
Calibration Of SF6 Gas Density
Gauge And Its Pressure Switch Test
|
||
EHV.GIS.CR
|
Contact Resistance Test
|
||
EHV.GIS.CB
|
CB Test
|
||
EHV.GIS.DS&ES
|
ES & DS Test
|
||
EHV.GIS.ES.10kV
|
ES 10 kV Test
|
||
EHV.GIS.CT.TEST
|
CT Test
|
||
EHV.GIS.CT.SI
|
CT Secondary Circuit Injection
Test
|
||
EHV.GIS.CT.LR
|
CT Loop Resistance And Single
Earth Point Test
|
||
EHV.GIS.CT.PI
|
CT Primary Injection Test
|
||
EHV.GIS.VT.TEST
|
VT Test
|
||
EHV.GIS.VT.SI&LR
|
VT Secondary Circuit Injection
& loop Resistance Test
|
||
EHV.GIS.HVT
|
HV Test
|
||
EHV.GIS.A
|
Annunciator Test
|
||
EHV.GIS.MCB
|
MCB And MCCB Test
|
||
EHV.GIS.M
|
Meter Test
|
||
EHV.GIS.AUX
|
Auxiliary Relay Test
|
||
EHV.GIS.MS
|
Metrosil Test
|
||
EHV.GIS.LCC.SCH
|
LCC Scheme Check
|
||
HV.GIS
|
High Voltage GIS
|
HV.GIS.SF6.TEST
|
SF6 Gas Purity And Dew Point Test
|
HV.GIS.SF6.LEK
|
SF6 Gas Leakage Test
|
||
HV.GIS.SF6.DG
|
Calibration Of SF6 Gas Density
Gauge And Its Pressure Switch Test
|
||
HV.GIS.CR
|
Contact Resistance Test
|
||
HV.GIS.CB
|
CB
Test
|
||
HV.GIS.DS&ES
|
ES & DS Test
|
||
HV.GIS.ES.10kV
|
ES 10 kV Test
|
||
HV.GIS.CT.TEST
|
CT Test
|
||
HV.GIS.CT.SI
|
CT Secondary Circuit Injection
Test
|
||
HV.GIS.CT.LR
|
CT Loop Resistance And Single
Earth Point Test
|
||
HV.GIS.CT.PI
|
CT Primary Injection Test
|
||
HV.GIS.VT.TEST
|
VT Test
|
||
HV.GIS.VT.SI&LR
|
VT Secondary Circuit Injection
& Loop Resistance Test
|
||
HV.GIS.HVT
|
HV Test
|
||
HV.GIS.A
|
Annunciator Test
|
||
HV.GIS.MCB
|
MCB And MCCB Test
|
||
HV.GIS.M
|
Meter Test
|
||
HV.GIS.AUX
|
Auxiliary Relay Test
|
||
HV.GIS.MS
|
Metrosil Test
|
||
HV.GIS.LCC.SCH
|
LCC Scheme Check
|
||
33.SWG
|
33 kV Switch Gear
|
33.SWG.BB.CR
|
BB Contact Resistance Test
|
33.SWG.CB
|
CB Test
|
||
33.SWG.ES.CR
|
ES Contact Resistance
|
||
33.SWG.M
|
Meter Test
|
||
33.SWG.CT.TEST
|
CT Test
|
||
33.SWG.CT.SI
|
CT Circuit Secondary Injection
Test
|
||
33.SWG.CT.LR
|
CT Loop Resistance And Single
Earth Point Test
|
||
33.SWG.CT.PI
|
CT Primary Injection Test
|
||
33.SWG.VT.TEST
|
VT Test
|
||
33.SWG.VT.SI&LR
|
VT Secondary Injection & Loop
Resistance Test
|
||
33.SWG.HVT
|
HV Test
|
||
33.SWG.MCB
|
MCB And MCCB Test
|
||
33.SWG.AUX
|
Auxiliary Relay Test
|
||
33.SWG.SCH
|
Scheme Check
|
||
13.SWG
|
13.8 kV Switch Gear
|
13.SWG.BB.CR
|
BB Contact Resistance Test
|
13.SWG.CB
|
CB Test
|
||
13.SWG.ES.CR
|
ES Contact Resistance
|
||
13.SWG.M
|
Meter Test
|
||
13.SWG.CT.TEST
|
CT Test
|
||
13.SWG.CT.SI
|
CT Circuit Secondary Injection
Test
|
||
13.SWG.CT.LR
|
CT Loop Resistance And Single
Earth Point Test
|
||
13.SWG.CT.PI
|
CT Primary Injection Test
|
||
13.SWG.VT.TEST
|
VT Test
|
||
13.SWG.VT.SI&LR
|
VT Secondary Injection & loop Resistance Test
|
||
13.SWG.HVT
|
HV Test
|
||
13.SWG.MCB
|
MCB And MCCB Test
|
||
13.SWG.AUX
|
Auxiliary Relay Test
|
||
13.SWG.SCH
|
Scheme Check
|
||
EHV.LP
|
EHV Line Protection
|
EHV.LP.DIF-1.A
|
Set 1 Line Differential Relay
Acceptance Test
|
EHV.LP.DIF-1.F
|
Set 1 Line Differential Relay
Final Setting Test
|
||
EHV.LP.DIF-2.A
|
Set 2 Line Differential Relay
Acceptance Test
|
||
EHV.LP.DIF-2.F
|
Set 2 Line Differential Relay
Final Setting Test
|
||
EHV.LP.DIST-1
|
Set 1 Distance Relay Test
|
||
EHV.LP.DIST-2
|
Set 2 Distance Relay Test
|
||
EHV.LP.MULTI-1.A
|
Main 1 Multifunction Relay
Acceptance Test
|
||
EHV.LP.MULTI-1.F
|
Main 1 Multifunction Relay Final
Setting Test
|
||
EHV.LP.MULTI-2.A
|
Main 2 Multifunction Relay
Acceptance Test
|
||
EHV.LP.MULTI-2.F
|
Main 2 Multifunction Relay Final Setting Test
|
||
EHV.LP.UV/OV
|
Undervoltage And Overvoltage Relay
Test
|
||
EHV.LP.AR
|
Automatic Recloser Test
|
||
EHV.LP.ASYNC
|
Auto Synchronizing Relay Test
|
||
EHV.LP.THOL
|
Thermal Overload Relay Test For
Underground Cable
|
Sunday, 10 January 2016
Required Electrical & Mechanical tests for Substation Equipments(2)
Subscribe to:
Post Comments (Atom)
The necessary response to substation problems
When it comes to power distribution, substations are the backbone of our grid. Keeping them in optimal condition is essential to ensure re...
Labels
- substation material (7)
- transformers (6)
- cable (5)
- gas insulated switchgear (5)
- transmission lines (4)
- SF6 (3)
- inspection (3)
- safety (2)
- specifications (2)
- current transformer (1)
- education (1)
- electrical hazard (1)
- grounding (1)
-
Trench Construction: The cable trench may be precast (Preferred) or poured in place (Non Preferrred). Poured-in-place trench walls t...
-
1. PURPOSE: The purpose of this procedure is to verify functions of Metal Enclosed Bus Duct. 2. AP...
-
PHOTO for ABB xlpe-submarine cable Scope This specification defines the mandatory requirements for the design, manufacture,factory inspect...