Transformers installation, shipment ,handling instructions & site tesing
•
•
1 comment
Substation Blog for All
| adv. |
Application
|
Test Voltage
|
Criteria
|
After repairs – Sheath
|
1kV Megger 1 minute
|
10 meg-ohms min.
|
After repairs – Insulation
|
5kV Megger 1 minute
|
1000 meg-ohms min.
|
After repairs – Insulation
|
5kV DC 1 minute
|
5.0 μA (micro-amps) max.
|
Application
|
Test Voltage
|
Criteria
|
New cables – Sheath
|
1kV Megger 1 minute
|
100 meg-ohms min.
|
New cables – Insulation
|
10kV DC 15 minute
|
1.0 μA (micro-amps) max
|
New cables – Insulation
|
10kV DC 15 minute
| 1000 meg-ohms min. |
Application
|
Test Voltage
|
Criteria
|
11kV new cables
|
5kV Megger 1 minute
|
100 meg-ohms.
|
11kV after repairs
|
5kV Megger 1 minute
|
100 meg-ohms.
|
33kV – no TF’s connected
|
5kV Megger 1 minute
|
1000 meg-ohms.
|
33kV – with TF’s connected
|
5kV Megger 1 minute
|
15 meg-ohms.
|