Showing posts with label gas insulated switchgear. Show all posts
Showing posts with label gas insulated switchgear. Show all posts
Monday, 8 January 2018
Sunday, 10 January 2016
Gas Insulated Swichgear ( GIS) - GENERAL EARTHING INFORMATION
Earthing and return current conductors
Earthing conductors
Earthing conductors interconnect the GIS enclosure at numerous points with the earthing net (multipoint earthing). Being a component of the earthing system they effectively help to avoid dangerous touch voltages during a short circuit, and to keep HF transient overvoltages on a sufficiently low level during normal service. To meet these requirements they shall have low impedances at 50/60 Hz as well as in the HF range.
Tuesday, 3 November 2015
The Gas Insulated Switchgear (GIS)
· Joints at interfaces, mechanical linkages, couplings, SF6 gas piping, cabling, wiring, grounding materials etc. required for proper and satisfactory operation.
· The GIS shall be of compact and modular design with individual equipment modules connected together to form a complete assembly. However, combined disconnect switch and grounding switch, cable termination, PT, exit bus duct and CT (with cores located within gas compartment) shall be in separate gas tight compartment. If, CT is installed in breaker gas compartment; insulation class for CT shall be class F. of either single-phase enclosure type or three-phase enclosure type for voltage levels of 230kV and below. of single-phase enclosure type for voltage level of 380kV. Installed on suitable pads or supporting frames/structures with provision for leveling, including fasteners to foundation, which shall also be included in the supply. Support-structures shall be designed and fabricated to withstand the short circuit forces of the ground fault current.
· GIS shall having expansion joints and flexible connections, where several enclosures are connected in the longitudinal direction, such as main bus. Expansion joints provided for installation alignment shall be locked in place when alignment is complete. Expansion joints for compensation of thermal expansion and erection tolerances shall have
· the means to preserve mechanical integrity of the enclosure and the plug-in contacts for the conductor. Provided with galleries, stairways, movable platform or walkways for accessing the equipment above two meters for maintenance and operation.
· All structures, movable platform, galleries, stairways and walkways shall have grounding provision and shall conform to the relevant Occupational Safety and Health Administration (OSHA) regulations.
· For single-phase type GIS, creation of single gas zone by external piping connection between the phases is not acceptable. Also, external piping connection (with normally open valve) to create common gas zone (between same phase) in single-phase type GIS is not acceptable.
· The GIS enclosure shall be safe to touch and fully ensure operational security and personnel safety under all normal and fault conditions with the maximum allowed induced voltage in the enclosure of 65 volts.
· The switchgear and all its components and accessories shall be designed for minimum maintenance during service. The manufacturer shall state the minimum interval between minor inspections (which will be restricted to visual checking and adjustments of external parts only) and major inspection/overhaul, including refilling or replenishment of gas and cleaning of the contaminant or filter in the circuit breaker chamber(s).
· Suitable openings shall be provided in the circuit breaker, disconnect and grounding switch modules for major inspection/adjustments.
· All motors shall be in accordance with IEC 60034. The bearings and other such parts shall be permanently lubricated for the entire service life. Padlocks shall be made of stainless steel or brass.
The GIS interface points shall be carefully coordinated with other equipment such as overhead lines, cables, transformers, reactors, capacitor banks, etc., supplied by other manufacturers in order to ensure full compatibility. The design criteria for outdoor

Sunday, 6 September 2015
The Gas Insulated Switchgear (GIS)
·
The
Gas Insulated Switchgear (GIS) shall be a complete unit comprised of main
equipment, all control, monitoring, protection, measuring and auxiliary devices
and systems including interconnections, all termination
·
Joints
at interfaces, mechanical linkages, couplings, SF6
gas piping, cabling, wiring, grounding
materials etc. required for proper and satisfactory operation.
·
The
GIS shall be of compact and modular design with individual equipment modules
connected together to form a complete assembly. However, combined disconnect
switch and grounding switch, cable termination, PT, exit bus duct and CT (with cores located within gas
compartment) shall be in separate gas tight compartment. If, CT is installed in
breaker gas compartment; insulation class for CT shall be class F. of either
single-phase enclosure type or three-phase enclosure type for voltage levels of
230kV and below. of single-phase enclosure type for voltage level of 380kV. Installed
on suitable pads or supporting frames/structures with provision for leveling,
including fasteners to foundation, which shall also be included in the supply.
Support-structures shall be designed and fabricated to withstand the short
circuit forces of the ground fault current.
·
GIS
shall having expansion joints and flexible connections, where several
enclosures are connected in the longitudinal direction, such as main bus.
Expansion joints provided for installation alignment shall be locked in place
when alignment is complete. Expansion joints for compensation of thermal
expansion and erection tolerances shall have the
means to preserve mechanical integrity of the enclosure and the plug-in
contacts for the conductor. Provided with galleries, stairways, movable
platform or walkways for accessing the equipment above two meters for maintenance
and operation.
·
All structures, movable platform, galleries,
stairways and walkways shall have grounding provision and shall conform to the
relevant Occupational Safety and Health Administration (OSHA) regulations.
·
For
single-phase type GIS, creation of single gas zone by external piping
connection between the phases is not acceptable. Also, external piping
connection (with normally open valve) to create common gas zone (between same
phase) in single-phase type GIS is not acceptable.
·
The
GIS enclosure shall be safe to touch and fully ensure operational security and
personnel safety under all normal and fault conditions with the maximum allowed
induced voltage in the enclosure of 65 volts.
·
The
switchgear and all its components and accessories shall be designed for minimum
maintenance during service. The manufacturer shall state the minimum interval
between minor inspections (which will be restricted to visual checking and
adjustments of external parts only) and major inspection/overhaul, including refilling
or replenishment of gas and cleaning of the contaminant or filter in the
circuit breaker chamber(s).
·
Suitable
openings shall be provided in the circuit breaker, disconnect and grounding
switch modules for major inspection/adjustments.
·
All
motors shall be in accordance with IEC 60034. The bearings and other such parts
shall be permanently lubricated for the entire service life. Padlocks shall be made
of stainless steel or brass.
·
The
GIS interface points shall be carefully coordinated with other equipment such
as overhead lines, cables, transformers, reactors, capacitor banks, etc.,
supplied by other manufacturers in order to ensure full compatibility. The
design criteria for outdoor portion of the GIS bus duct leading to SF6-to-Air Overhead Line Termination / SF6-to-Oil
Transformer Termination shall be as mentioned in clause 4.2.2 and in the data
schedule.
·
All
modules of the switchgear and components of the same rating and construction,
which may need to be replaced, shall be strictly interchangeable.
·
To
facilitate transport and handling, lifting eyes or other suitable attachments
shall be provided with each GIS module.
·
Each
module of switchgear, consisting of individual elements intended to be directly
connected together, shall be constructed as a transportable assembly suitable
for shipping and transportation without being dismantled.
·
All
new gaskets, sealants and desiccants for permanent sealing of all field joints
and all access covers, removed during assembly, shall also be provided.
·
The
GIS shall be designed per IEC 62271-203 or ANSI/IEEE C37.122 standard. The
enclosure shall be capable of sustaining without damage all mechanical,
electrical and thermal shocks that may occur in service during normal and fault
conditions, including pressure effects of internal fault arc current of
specified short circuit level and time. The enclosure assembly, material and
design shall be such as to minimize induced electrical losses and heating
effects which could occur in service under normal and fault conditions.
·
Joints
and couplings between dissimilar metals shall be avoided to prevent galvanic
corrosion.
·
All
supporting steel work shall be hot-dip galvanized
·
A
partition separating a compartment filled with insulating gas from a neighboring
compartment such as a cable box, filled with liquid, shall not show any leakage
affecting the dielectric properties of the two media.
·
All
welding in GIS shall conform to Section IX of ASME code or equivalent. The
number of welds shall be kept to a minimum. At least 10% of all welds must be
subject to non-destructive testing by X-ray or ultrasound and all records of
these must be made available.
·
The
construction and thickness of the GIS enclosure and air storage tank of the
pneumatic operating mechanism shall conform to ANSI/ASME Boiler and Pressure
Vessel Code, and ANSI/ASME B31.1 or equivalent.
·
All
current carrying parts shall be made of electrolytic grade copper or aluminum
alloy. All interconnecting sections of current transferring parts shall be
silver-plated.
·
All
piping for SF6 gas,
hydraulic and pneumatic operating mechanism including their fittings shall be
made of copper, brass or stainless steel.
·
All
external connectors and terminal pads shall be made of copper or aluminum with
tin-plating and designed per NEMA CC1 and NEMA CC3. Terminal pads shall have 4 holes.
·
Rated
interrupting current of the auxiliary contacts shall be not less than 10Adc.
·
The
specific ratings of the GIS equipment shall be as specified in the data schedule.
·
The
switchgear shall be capable of carrying the specified rated current continuously
at the design ambient and specified ambient conditions without temperature rise of various parts
exceeding the limits stated in IEC 60694 or equivalent ANSI standards. The
maximum
·
All
equipment and components of the switchgear including bus support insulators
shall be free of partial discharges when operated at the rated voltage. The
partial discharge intensity at ll0% rated voltage shall not exceed 10 pC with a
maximum background level of 5pC.
·
Future
alterations and extensions can be undertaken in either direction by GIS
manufacturers other than the original manufacturer.
·
Maintenance
or removal of a disconnect switch or circuit breaker will not involve removal
from service of adjacent disconnect switch or main bus sections.
·
Separate
GIS bus link module shall be provided at both ends of the GIS to avoid
modification of the existing bus for future extension of the GIS buses by GIS
manufacturers other than the original manufacturer.
·
Adequate
clearances around GIS shall allow free movement of SF6 gas service cart.
·
Two
maintenance grounding switches shall be provided across each circuit breaker to
measure the contact resistances of circuit breaker at site.
·
Sufficient
clearances around bushing for cable HV AC testing shall be provided.
Adequate facilities shall be made available for neat
storage of HV AC cable-test bushing in the substation
PACKING AND SHIPPING FOR NEW EQUIPMENTS
For another Equipment check our Archive ,Labels $ search
All equipment/material shall be delivered within a period not exceeding two (2)years from date of completion of manufacture.
·
Export packing and shipping shall be adequate for sea transport
and handling up to site
·
Each assembly or component shall be skidded, crated, boxed or
otherwise suitably protected against damage or loss during shipment and to
facilitate field hand storage.
·
All openings shall be
effectively sealed with temporary closures to
prevent entry of dust, dirt, moisture and other foreign matter.
Each crate or container shall be marked with the number of pieces contained therein,
the manufacturer’s catalog number and description of the content, the manufacturer's
name, Country of origin, TBU Item Number, TBU Purchase Order Number, Contract
No. or J.O. No. and the gross weight in kg.
·
Additional handling and shipping instructions if specified in
SOW/TS or in
Purchase Order and/or by Materials Management Department, or other concerned departments,
shall also be applicable.
·
All documentations such as manuals, catalogues, etc. shall be
submitted
·
in hard copy and electronic copy in Acrobat Reader format.
·
All dimensions shall be in SI units.
prevent entry of dust, dirt, moisture and other foreign matter.
Each crate or container shall be marked with the number of pieces contained therein, the manufacturer’s catalog number and description of the content, the manufacturer's name, Country of origin, TBU Item Number, TBU Purchase Order Number, Contract No. or J.O. No. and the gross weight in kg.
Purchase Order and/or by Materials Management Department, or other concerned departments, shall also be applicable.
Subscribe to:
Posts (Atom)
The necessary response to substation problems
When it comes to power distribution, substations are the backbone of our grid. Keeping them in optimal condition is essential to ensure re...
Labels
- substation material (7)
- transformers (6)
- cable (5)
- gas insulated switchgear (5)
- transmission lines (4)
- SF6 (3)
- inspection (3)
- safety (2)
- specifications (2)
- current transformer (1)
- education (1)
- electrical hazard (1)
- grounding (1)
-
Trench Construction: The cable trench may be precast (Preferred) or poured in place (Non Preferrred). Poured-in-place trench walls t...
-
PHOTO for ABB xlpe-submarine cable Scope This specification defines the mandatory requirements for the design, manufacture,factory inspect...
-
1. PURPOSE: The purpose of this procedure is to verify functions of Metal Enclosed Bus Duct. 2. AP...