Single-core underground power cables with two-points bonding induce currents in their metallic sheaths. The sheath induced currents are undesirable and generate power losses and reduce the cable ampacity. The values of the sheath losses in some cases could be greater than conductor losses, depending on various factors. Such these factors are type of cable layouts, cable parameters, cable spacing, sheath resistance, phase rotation, conductor current and cable armoring
SHEATH BONDING ARRANGEMENTS
Sheath bonded at two-points
In which the sheaths of three separate cables will be connected together at both ends of the
run. For safety reasons one end of the sheaths must also be ear thed. This system
doesn’t allow high values of the induced voltages in the metallic sheaths. In this situation, sheath
circulating currents appear because of there is a closed circuit between the sheath and the return
path through the ground.
Sheath bonded at one end only
In which the sheaths of three separate cables will be connected together and earthed at one
point only along their length. At all other points, a voltage will appear from sheath to
ground that will be a maximum at the farthest point from the ground bond. Since there is no closed
sheath circuit current no sheath circulating current loss occurs, but sheath eddy loss will still be
present.
Sheath cross bonded
Cross bonding of single-core cable sheaths is in use for many years. In which, each sheath
circuit contains one section from each phase such that the total voltage in each sheath circuit sums
to zero. If the sheaths are then bonded and earthed at the end of the run, the net voltage in the loop
and the circulating currents will be zero and the only sheath losses will be those caused by eddy
currents.
FACTORS AFFECTING THE SHEATH LOSSES IN SINGLE-CORE UNDERGROUND
POWER CABLES WITH TWO-POINTS BONDING
·
Cable layouts formation as Trefoil
and flat formations are usually used in practice
·
Cable conductor resistivity
·
Cable spacing
·
Sheath resistance
·
Phase rotation
·
Conductor current
·
Cable armoring
CONCLUSION
1. It must pay attention to
sheath losses in single-core cables with two-points bonding as their values
could be reached to more than the conductor losses.
2. The sheath eddy losses
could be neglected w.r.t the sheath circulating losses at high sheath
3. resistance values and
high conductors spacing
4. Sheath eddy losses are
inversely proportional to sheath resistance, cable conductor resistivity
5. and conductors spacing,
while they are proportional to conductor current.
6. Sheath circulating
losses are proportional to the conductors spacing, and conductor current and
can be reduced by large increase in sheath resistance or large reduce in the
sheath resistance but the later leading to high circulating current.
7. Phase rotation plays a
great role in determination of the sheath circulating losses in flat layout.
8. Trefoil formation
introduces symmetrical values of losses in its sheathes than flat formation
9. addition to the total
sheath losses in the trefoil are lower than flat layout.
No comments:
Post a Comment