Adorama.com INT

2

money

Wednesday 13 January 2016

Cable sheath bonding


Single-core underground power cables with two-points bonding induce currents in their metallic sheaths. The sheath induced currents are undesirable and generate power losses and reduce the cable ampacity.  The values of the sheath losses in some cases could be greater than conductor losses, depending on various factors. Such these factors are type of cable layouts, cable parameters, cable spacing, sheath resistance, phase rotation, conductor current and cable armoring

SHEATH BONDING ARRANGEMENTS


Sheath bonded at two-points

In which the sheaths of three separate cables will be connected together at both ends of the 
run. For safety reasons one end of the sheaths must also be ear thed. This system 
doesn’t allow high values of the induced voltages in the metallic sheaths. In this situation, sheath 
circulating currents appear because of there is a closed circuit between the sheath and the return
path through the ground. 

Sheath bonded at one end only

In which the sheaths of three separate cables will be connected together and earthed at one 
point only along their length. At all other points, a voltage will appear from sheath to 
ground that will be a maximum at the farthest point from the ground bond. Since there is no closed 
sheath circuit current no sheath circulating current loss occurs, but sheath eddy loss will still be 
present.

Sheath cross bonded

Cross bonding of single-core cable sheaths is in use for many years. In which, each sheath 
circuit contains one section from each phase such that the total voltage in each sheath circuit sums 
to zero. If the sheaths are then bonded and earthed at the end of the run, the net voltage in the loop 
and the circulating currents will be zero and the only sheath losses will be those caused by eddy 
currents.





FACTORS AFFECTING THE SHEATH LOSSES IN SINGLE-CORE UNDERGROUND
POWER CABLES WITH TWO-POINTS BONDING
·         Cable layouts formation as Trefoil and flat formations are usually used in practice
·         Cable conductor resistivity
·         Cable spacing
·         Sheath resistance
·         Phase rotation
·         Conductor current
·         Cable armoring
CONCLUSION
1.     It must pay attention to sheath losses in single-core cables with two-points bonding as their values could be reached to more than the conductor losses.
2.     The sheath eddy losses could be neglected w.r.t the sheath circulating losses at high sheath 
3.     resistance values and high conductors spacing
4.     Sheath eddy losses are inversely proportional to sheath resistance, cable conductor resistivity 
5.     and conductors spacing, while they are proportional to conductor current.
6.     Sheath circulating losses are proportional to the conductors spacing, and conductor current and can be reduced by large increase in sheath resistance or large reduce in the sheath resistance but the later leading to high circulating current.
7.     Phase rotation plays a great role in determination of the sheath circulating losses in flat layout.
8.     Trefoil formation introduces symmetrical values of losses in its sheathes than flat formation
9.     addition to the total sheath losses in the trefoil are lower than flat layout.

No comments:

omar

Libertex [CPS] WW

Sponcer

button

tele

Lycamobile's SIM Only Plan For $9.90 - Limited Offer - 66% off on SIM+Plan. Grab your Prepaid SIM Deal now!

The necessary response to substation problems

  When it comes to power distribution, substations are the backbone of our grid. Keeping them in optimal condition is essential to ensure re...