SPONSOR |
Substation Grounding
The
grounding connections provided to substation equipment and structures fall under
two categories, namely
a.
Safety Grounds
b.
System Grounds
System
ground is normally for neutral grounding and safety ground is for equipment grounding.
Minimum conductor size for equipment safety grounding.
All
safety ground termination shall be made directly on to the ground grid. All
system ground shall be terminated on to a ground rod interconnected to the grounding
grid.
SOIL
RESISTIVITY MEASUREMENT
Measurement
· A number of measuring techniques are
described in detail in ANSI/IEEE 8. The Wenner's four-pin method as described
in ANSI/IEEE 8shall be used for measurement of soil resistivity. As many
readings as required for various spacing and depth, in all the eight
directions, sufficient to model the soil shall be carried out.
· Soil resistivity readings shall
normally be taken under dry conditions, during Summer months, if possible,
However the same shall not affect the project’s schedule.
· Fill up soil resistivity shall be
carried by soil modeling in laboratories on samples dried to 2% moisture
content after compaction.
· Soil resistivity measurement shall also
be carried out before and after fill up and compaction of soil at site.
Interpretation
of Test Results
For
soils with resistivity value less than 500 Ohm, if the difference between the highest
and the lowest readings are within 30 % then the soil can be considered as uniform
soil. For soils with resistivity value greater than 500 Ohm, if the difference
between the highest and the lowest readings are within 20 % then the soil can
be considered as uniform soil. For uniform soils, the mean value shall be considered
as soil resistivity value. In case of wide variations in field readings, computer
software alone shall be used to simulate two-layer model or multi-layer soil
model. Two-layer soil models are good approximation of many soil structures, while
multi-layer soil models may be used for more complex soil conditions. Software
shall be based on IEEE-80.
Backfill
Material
Backfill
material shall have possibly the same soil resistivity or better than that of
the original soil. In case of considerable backfill the soil resistivity shall
be taken after completion of the backfill compaction. The same shall be used
for grounding calculations. In case of delay of backfill activity at site the
estimated value of resistivity of the backfill material or that of the existing
soil whichever is higher shall be used for grounding calculations.
SELECTION
OF GROUNDING CONDUCTOR MATERIAL, SIZE AND JOINTS
Basic
Requirements
- · Copper material shall be used for grounding.
- · Soft drawn, stranded copper shall be used for the ground grid conductors.
- · The conductor shall be round shaped for maximum cross-sectional contact with the ground. In coastal zone with low soil resistivity, tinned copper conductor shall be used. Copper-clad steel shall be used for ground rods.
- · Each element of the ground system (including grid proper, connecting ground leads, and electrodes) shall be so designed that it shall :
- · Resist fusing and deterioration of electric joints under the most adverse combination of fault-current magnitude and fault duration to which it might be subjected.
- · Be mechanically rugged to a high degree, especially in locations exposed to physical damage.
- · Have sufficient conductivity so that it will not contribute substantially to dangerous local potential differences.
Equipment
grounding details
Steel
Structures and Switch Racks
Switch
racks and every steel structure that supports insulators or electrical
equipment shall be grounded by means of bolted connections at two (2)
diagonally opposite legs. Equipment mounted on steel supporting structures
shall have separate grounding conductors. The pigtail ground conductor shall be
supported on the structure at 1.0 meter intervals by clamps. Casting pigtail
conductor inside the steel structure concrete foundation is not acceptable.
Fences /
Gates
If
space permits a perimeter ground conductor shall be laid which follows the
fence
line and the gate in any position (open or close) and the fence then shall be
bonded electrically at corner posts, gate posts and every alternate line post.
The gates shall be bonded to the gateposts with a flexible copper cable or
braid.
The
barbed wire on the top of the SSD (Safety and Security Directive) type
fence/boundary wall, if applicable, shall be bonded to the
grounding grid.
Cables
Metallic
cable sheaths shall be effectively grounded by connecting a flexible braid to the
sheath to eliminate dangerous induced voltages to ground.
Control
Cables
Metallic
sheath of control cables shall be grounded at both ends to the grounding grid
via ground busbar in the cubicle.
Power
Cables
a. Sheath of Power cables rated 69kV to 380kV shall be grounded directly
from one end and through SVL(Sheath
Voltage Limiters) from the other
b.
Grounding of sheath of single core cables rated for 34.5kV and 13.8kV shall be from
One end only.
c.
Sheath of three core cables rated for 13.8kV shall be grounded at both ends.
If ring type CTs are installed on power
cables, the grounding of sheath shall be done such that the sheath current to
ground will not influence CT secondary current.
Instrument
Cables
Instrument
cables carrying analog or digital signals shall have their metallic screening
grounded at one point by means of PVC insulated grounding wire connected to
separate instrument ground bar which is insulated from cubicle ground.
Signal
Cables
All
signal cables used in telemetering and communications shall have their shield
grounded at one end only to reduce interference from stray sources.
Cable Tray
System
Cable
tray system shall be grounded with bare copper conductor of 50mm² size at
both
ends and shall be bonded across gaps including expansion gaps
Substation
Buildings
Substation
buildings shall be encircled by a grounding conductor.
Reinforcement
bars of the substation buildings and equipment foundation in the yard shall be
connected to the main grounding grid at least at two diagonally opposite
points.
For
grounding of the electrical apparatus installed inside substation
buildings
two separate exposed copper conductors/strips of size per manufacturer
recommendation, each connected to the grounding grid at two (2) different
points shall be laid. The grounding grid shall be laid inside the substation
buildings and
it
shall be connected to the main grid outside the buildings, at minimum two
points.
Metal
building(s)
·
Metal
buildings shall be grounded at each substructure column with a minimum size of
l20mm² bare copper conductor.
·
Angle
irons installed on indoor trenches to support the metallic covers shall also be
grounded at both ends.
·
Metallic
doors in substation buildings shall be grounded with a flexible copper cable or
braid.
HVAC
All
air conditioning ducts inside the control building(s) shall be grounded at both
ends and cross bonded at all joints and across the non-metallic duct connecting
Air Handling Unit (AHU).
Grounding
of control panels, Operating Mechanism Housing, Box, etc and other equipments
associated with HVAC shall be done
Metallic
Conduits
All
metallic conduits shall be connected to the grounding grid at each manhole or
at terminating points by using a conductor size of 50 mm². Conduits terminating
in metal junction boxes shall be grounded by means of grounding studs or brazed
connections. Where several conduits or junction boxes are located adjacent to
each other, an adequately sized solid wire shall be used to interconnect the
boxes. It shall be connected to grounding system at one single point.
Circuit
Breakers and Disconnect Switches
·
All
circuit breakers and disconnect switches shall be grounded at two diagonally opposite
corners from two separate points of the grounding grid. Further grounding switch blades of Disconnect Switch
shall be directly grounded to grounding grid.
·
Good
electrical connection shall be maintained between the steel structure and any bolted
accessories mounted on it.
·
Operating
Handles for Outdoor Switches as a large percentage of fatal accidents from
voltage gradients are associated with manual operating handles of disconnect
switches, etc.
·
A
metal grounding plate or mat (operating platform), shall be placed where the
operator must stand on it to operate the device. The operating handles shall be
grounded by connecting a ground conductor (preferably flexible wire, braid
strap) from the vertical operating pipe to the supporting structure, then
continuing another stranded ground conductor to the switch operating platform.
It is reiterated that the operating handle and the platform shall not be
directly connected to the grounding grid but instead both connected to the
support structure which in turn shall be connected to the grounding grid at
least at two diagonally opposite points.
Terminal
Transmission Tower Grounding
Terminal
transmission towers located adjacent to the substation shall be connected to
the
substation grounding grid at two diagonally opposite points. The shield wire
shall
be
connected to the tower structure, which in turn is connected to the grounding
grid.
Lightning Masts
Metal
lightning masts shall have one safety ground.
Ring Main
Unit (RMU)
The
RMU inside the substation, if applicable, shall have two safety ground connections.
Oil Tanks
and Oil /Water Pipings
All
oil tanks shall be grounded at two points with bolted cable connections to two
different
points of the grounding grid. Oil piping shall be grounded at intervals of
12m.
Runs shorter than l2m shall be grounded at least at two points. Water piping
shall
be connected to the grounding system at all service points. In addition, two
copper
conductors of adequate size, shall be connected to the main water pipe from two
separate points of the grounding grid.
Metal Clad
Switchgear
Metal
Clad switchgear shall have two safety grounds connected to the switchgear grounding
bus. Withdrawable circuit breakers and PTs shall be provided with reliable connection
to the ground bus. Grounding via the roller wheels and the rail is not
acceptable.
Grounding
of Lighting Equipment
Grounding
of the lighting fixtures, lamp holders, lamps, receptacles and metal poles
supporting lighting fixtures shall be per Article 250 and 410 of NEC (NFPA 70).
Portable
Equipment
Portable
electrical equipment shall be grounded in accordance with the
applicable
requirements of Articles 250 of the NEC (NFPA 70).
Temporary
Grounding
All
the components used for temporary protective system shall meet IEEE Std. 1246,
“Guide
for Temporary Protective Grounding System Used in Substations”.
Instruments,
Relays and Meters
Instruments,
meters and relays shall be grounded in accordance with the requirements of the
NEC, Articles 250-120 to 126 and Articles 170 to 178.
Equipment
Requiring both Safety and System Grounds
All
operating grounds shall have their connections made to the grounding rods,
which in turn shall be connected to the grounding grid.
Power
Transformers
·
Power
transformer tanks shall be safety grounded at two points diagonally opposite to
each other. These connections shall be made from two different points of the
grounding grid.
·
A
separate system ground shall be provided for the neutral of the transformer by
means of two (2) stranded copper wires. The neutral copper wire shall be sized
for the system fault level.
·
The
neutral grounding wires shall be insulated from the transformer tank by support
insulators mounted on the tank wall and shall be connected to the grounding
grid directly.
·
Independently
mounted radiator bank and LPOF/XLPE cable termination
·
boxes
shall be separately grounded at two diagonally opposite locations.
·
Tertiary
windings and stabilizing windings shall be grounded per IEC60076-3, Annexure B.
Instrument
Transformers
·
Potential
and current transformers shall have their metal cases grounded.
·
The
grounding terminal of the potential transformers shall be connected to the
grounding grid.
·
The
neutral point of the secondary connections of potential and current
transformers shall be grounded to the ground grid in the control/relay room
instead of switchyard to reduce the transient overvoltages.
·
Other
requirements of instruments transformer grounding shall be per IEEE C57.13.3,
“Guide for Grounding of Instrument Transformer Secondary Circuits and Cases”.
Surge
Arresters
·
Where
surge counter and/leakage current indicating meters are installed, a 5 kV
insulated cable shall be used between arrester ground terminal and surge
counter. The surge monitor's ground terminal shall be connected to the ground
grid via two (2) 240 mm² stranded copper conductors.
·
The
system ground conductor shall be as short as possible, free of sharp bends, and
shall not be installed in metallic conduit. In addition, ground rods shall be
driven adjacent to the arrester connection to the grounding grid to provide the
lowest ground grid resistance at this point.
Station
Auxiliary Transformer
Station
auxiliary transformer shall be safety grounded at two locations diagonally opposite.
One system ground shall be directly connected to the neutral wye connected
windings that are to be solidly grounded.
Shunt
Capacitors
Shunt
capacitors are considered safety grounded when mounted on a metal structure
that
is connected to the grounding grid. One system ground conductor shall be connected
to the grounding grid when the capacitors are to be connected in a grounded
star configuration.
Coupling
Capacitor Voltage Transformers (CCVTs)
The
grounding terminal and neutral point of secondary connections of CCVT shall be
connected to the grounding grid similar to potential transformer as
No comments:
Post a Comment