⚡ Welcome to Substation Blog — Your resource for electrical engineering, safety & substation technology. About Us
Showing posts with label transformer shipping. Show all posts

Monday, 18 January 2016

Benefits of dry Air Filling in Transformer?

 •   •  No comments

Dry air must be used to ventilate the inside of the tank when it is opened for internal fitting. The air must have a dew point less than -40°C and sufficient airflow for the number of operators in the tank must be maintained.

Do never use nitrogen or other gases than air for ventilation

When opening the transformer tank, care must be taken to prevent moisture or dirt entering the transformer or moisture condensing in the transformer. If wet air enters the transformer, it may be cooled by the tank wall below its dew point and condensed, so it will reduce dielectric strength of the transformer
Dry air should be supplied through hand hole during working or inspection. Care especially must be taken not to drop tools or foreign substances. It is recommended that tools used in the tank be tied to worker with a cord. When the work in the tank is completed, the inside of the tank should be inspected. For inside cleaning, the dry, clean and lint-free cloths should be used.

Sunday, 3 January 2016

Impact recorders for transformers shipping

 •   •  No comments
Impact Recorders continually monitor and report in real-time the shock, vibration and environmental conditions experienced by structures, facilities or equipment during transit, storage and operation. ShockLog impact recorders register the direction, amplitude, and duration of impact force. Optional sensors record changes in temperature, humidity, atmospheric pressure, tilt and roll. A GPS/ GPRS tracking module is available to pinpoint the location of mishandling or exposure to adverse conditions.  impact recorders are acute impact detection devices, which help to deter, monitor and minimize damage at each link of your supply chain

types of impact recorders:
1- electronic
2- analog

Below is Sample of inspection report for electronic impact recorder

Featured Post

The necessary response to substation problems

  When it comes to power distribution, substations are the backbone of our grid. Keeping them in optimal condition is essential to ensure re...